- 7 -
Cont ...
Cold water connection:
2.27 The cold water supply: The supply must be air free and have a dedicated
connection to the tank which should be via a tank connector, positioned at a
slightly lower level (25 mm minimum) than the feed pipe to the hot water cylinder.
Do not connect to the mains.
2.28 Location: The pump must, for optimum performance, be sited as close as
possible to and never more than 4 metres from the HOT WATER cylinder. The
pump should always be sited BELOW the HOT WATER take-off from the cylinder.
2 LOCATION - TWIN PUMP
Positive Duty Twin Pump System
Fig. 5
Max. static inlet pressure 14 m
Outlet head must be
below bottom of cold
water tank and able
to pass a minimum
of 0.6 l/min of gravity
flow